Topic: DMD0477 Module Configuration for BX-4UT4TR, BX-4UT4TD1, and BX-4UT4TD2 Combination Universal Temperature Input / Discrete Output Modules |
||||||||||
|
||||||||||
When a Do-more CPU powers up and detects a new BX-4UT4TR, BX-4UT4TD1, or BX-4UT4TD2 module it will automatically create a module configuration and assign the required I/O mapping using the first 4 available WX (32-bit signed integer) locations, the first 4 available Y locations, and the first 8 available X (input bit) locations required by the module.
The default configuration has all of the channels disabled. Clicking the Enable *Click for Setup* button in the Module Configuration utility will open the following dialog where the default configuration can be changed. Click Enable Channel then select the type of temperature input probe or raw voltage range that will be used on this channel. Channel Type selects the type of input probe or raw voltage; Probe / Range selects the temperature range of the probe or voltage range respectively.
Once the Channel Type and Probe selection has been made, click Apply to Current Channel to use these selections for the current channel only, or Apply to All Channels to have these selections used for all of the input channels on the modules, or Cancel to exit the dialog and not retain any of the changes. The following table has all of the possible channel types and ranges:
|
||||||||||
|
||||||||||
|
||||||||||
The Analog Inputs 0-3 tab set the following options that are specific to the individual channels:
|
||||||||||
|
||||||||||
The Global Settings tab has settings that affect all of the channels on the module.
Temperature Scale selects whether the reported values for all of the channels will be in Degrees Fahrenheit or Degrees Celsius.
A/C Rejection selects the level of A/C noise rejection the A/D conversion will apply. The default value is for either 50 or 60 Hz @75dB powered systems. Select 60Hz @ 120dB for 60Hz powered systems or 50Hz @ 120dB for 50Hz powered systems for additional noise filtering.
|
||||||||||
|
||||||||||
Input Channel Wiring Diagrams:Channel is configured as a Thermocouple:
Channel is configured as 3-wire RTD or 4-wire RTD:
Channel is configured as 2-wire RTD:
Channel is configured as Thermistor:
Channel is configured as Voltage:
|
||||||||||
|
||||||||||
See Also:
|
||||||||||
|