Topic: DMD0474

Help File Version: 2.9.4.37

Module Configuration for BX-2AD2DA-3 and BX-4AD4DA-3 Modules
Combination Universal Current or Voltage Inputs / Universal Current or Voltage Outputs


When a Do-more CPU powers up and detects a new BX-2AD2DA-3 or BX-4AD4DA-3 module it will automatically create a module configuration and assign the required I/O mapping using the first 2 or 4 available WX (32-bit signed integer) locations, the first 2 or 4 available WY (32-bit signed integer) locations, and the first 2 or 4 available X (input bit) locations required by the module.

 

The default configuration has all of the input and output channels enabled in 0 - 5V mode with scaling disabled. Clicking the Edit Config button in the Module Configuration utility will open the following dialog where the default configuration can be changed.

 

 

The Analog Inputs 0-1 / 0-3 tab sets the following options that are specific to the individual channels:

Analog Input # selects the input type: (voltage) 0 - 5V, 0 - 10V, +/- 5V, +/- 10V, (current) 4 - 20mA or +/- 20mA.

 

Filter time is the amount of time (in seconds) over which to apply the filter. The filter operation applies 63.2% of the difference between the current analog circuit value and the last output value to the new output value over the duration of the filter time. Enabling the filter will dampen or slow down the changes in analog value to produce a more linear input value. This can be any positive value. A value of 0.0 will disable the filter.

 


The WX# group shows the range of values, the resolution, and the units / count of the raw input value based on the current Analog Input # selection. The range for bipolar voltage and current selections is -32768 to +32767; the range for unipolar voltage selections is 0 - 32767; the range for the unipolar current selection is 6553 - 32767.

 

This group also shows the X bit memory location for the Broken Transmitter indication (for the unipolar current selection), and the Out Of Range indication (for voltage ranges and the bipolar current range).

 


The RX# group (if automatic scaling is enabled for this channel) shows the Real numeric memory location where the scaled value will be stored in the CPU, the range of potential values, and the Units / Count based on the current scale factors.

 

Enable Scaling from WX# to RX# enables the automatic scaling of the raw input value (32-bit signed integer) to engineering units (32-bit real).

WX# Min / WX# Max the minimum and maximum raw values determined by the Analog Input # selection.

Counts / (mA or VDC) displays the WX#'s Min and Max values in terms of counts or milliamps / volts depending on the Analog Input selection type.

RX# Min / RX# Max contains the minimum and maximum values for the engineering units.

Clamp RX# (if enabled) and the calculated scaled value is lower than RX # Min or higher than RX# Max, the specified Min and Max values will be used.


 

The Analog Outputs 0-1 / 0-3 tab sets the following options that are specific to the individual channels:

Analog Output # (voltage) 0 - 5V, 0 - 10V, +/- 5V, +/- 10V, (current) 4 - 20mA or +/- 20mA.

 


The WY# shows the range of values, the resolution, and the units / count of the raw output based on the current Analog Output # selection. The range for bipolar voltage and current selections is -32768 to +32767; the range for unipolar voltage selections is 0 - 32767; the range for the unipolar current selection is 6553 - 32767.

 


The RY# group (if automatic scaling is enabled for this channel) shows the Real numeric memory location where the engineering unit value is stored in the CPU, the range of potential values and the Units / Count based on the current scale factors.

 

Enable Scaling from RY# to WY# enables the automatic scaling of the engineering units (32-bit real) to raw output value (32-bit signed integer).

RY# Min / RY# Max contains the minimum and maximum values for the engineering units.

 

WY# Min / WY# Max the minimum and maximum raw values determined by the Analog Output # selection.

Counts / (mA or VDC) displays the WX#'s Min and Max values in terms of counts or milliamps / volts depending on the Analog Output selection type.

 

Clamp WY# (if enabled) and the calculated scaled value is lower than WY # Min or higher than WY# Max, the specified Min and Max values will be used.


See Also:

BX-04AD-3 / BX-08AD-3 - BRX Universal Current / Voltage Input

 

BX-04DA-3 / BX-08DA-3 - BRX Universal Current / Voltage Output

 

BX-4AD4DA-3 / BX-2AD2DA-3 - BRX Combination Universal Current / Voltage Input and Output

 


BX-04UT / BX-08UT - BRX Universal Temperature Input

 

BX-4UT4DA-3 - BRX Combination Universal Temperature Input and Universal Current / Voltage Output

 

BX-4UT4TR - BRX Combination Universal Temperature Input and Relay Output

 

BX-4UT4TD1 - BRX Combination Universal Temperature Input and Sinking DC Output

 

BX-4UT4TD2 - BRX Combination Universal Temperature Input and Sourcing DC Output

 


BX-APAD (Active Pad)

See Also:

BX-04AD-1 / BX-04ADM-1 / BX-08AD-1 / BX-16AD-1 - BRX Current Input

 

BX-04AD-2B / BX-08AD-2B / BX-16AD-2B - BRX Voltage Input

 

BX-04DA-1 / BX-08DA-1 - BRX Current Output



BX-04DA-2B / BX-08DA-2B - BRX Voltage Output

 

BX-4AD2DA-1 / BX-2AD2DA-1 - BRX Combination Current Input and Output

 

BX-4AD2DA-2B / BX-2AD2DA-2B - BRX Combination Voltage Input and Output

 


BX-04THM / BX-08THM - BRX Thermocouple Input

 

BX-4THM4DA-1 - BRX Combination Thermocouple Input and Current Output

 

BX-06RTD - BRX RTD Input



BX-4RTD4DA-1 - BRX Combination RTD Input and Current Output

 

BX-08NTC - BRX NTC (Thermistor) Input