BX-MBIO Do-more Modbus Remote Base Controller Updated: 05/22/2018
Specifications Firmware      
The BX-MBIO is a remote base controller that can used by either a Modbus/TCP Client or a Modbus/RTU Client.

The BX-MBIO requires NetEdit3 (v3.16 or later) to setup its TCP/IP network configuration and configure any analog input or analog output modules that are attached.
 

Specifications  
Ethernet Interface RJ-45, 10/100Mbps, Auto MDI-X
Modbus/TCP Protocol
Serial Port Software Configurable for RS232 or RS-485 - 120Ω Termination resistor is available (software selectable)
Modbus/RTU Protocol
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Baud Rates
Odd, Even, No Parity / 7, 8 Data Bits / 1, 2 Stop Bits
Station Address Range: 1 - 247
Input Power 120-240 VAC (nominal), 85 - 264 VAC (tolerance), 47 - 63 Hz
Internal Micro fuse 250V, 2A, non-replaceable
Isolated User 24 VDC Output
(on A/C model)
24VDC @ 0.3mA, <1VP-P ripple, Integrated self-resetting short circuit protection
Operating Environment 0 – 60 ºC (32 – 140 ºF)
5% to 95% humidity (non-condensing)

no corrosive gases, pollution level=2

Vibration: IEC60068-2-6 (Test Fc)
Shock: IEC60068-2-27 (Test Ea)
Storage Temperature -20 ºC – 85 ºC  (-4 ºF – 185 ºF)
Firmware

BX-MBIO
Last Update   : 8 September 2021

F/W Version   : v4.2.134
Boot Version  : v4.2.16

View the BX-MBIO Revision History