PBC FAQ0001
27-Nov-2002
Q: My Profibus master is getting configuration errors with the
T1H-PBC. Module Status and Link Active are both solid green.
A: These lights are indeed indicating that there is a configuration
error. The most common mistake with the T1H-PBC is not realizing that
it takes 16DO (2 output bytes) all by itself, even with an empty base.
More than likely you have not configured these two output bytes;
especially if doing it manually. Many Profibus master configurators
allow you to browse to the slave. In most cases the browser will take
into account the 16DO.
PBC FAQ0002
22-Jan-2003
Q: Have there been any changes to the H2-PBC since the introduction
of H2-CTRIO?
A: No. (see our website for history).
PBC FAQ0003
12-Jul-2002
Q: Does the H2-PBC use the standard .gsd files for configuration, or
the older ET200 Type files by Siemens?
A: H2-PBC uses standard .gsd files. Siemens' COM Profibus software
supports these.
PBC FAQ0004 (see
also CTRIO FAQ0012, EBC FAQ0014, WinPLC FAQ0003)
06-Feb-2003
Q: CTRIO Workbench indicates that the CTRIO module is in "Startup"
mode and all of the configuration parameters are grayed out.
A: "Startup" mode indicates that CTRIO Workbench cannot
successfully communicate with the CTRIO. The problem is not between
CTRIO Workbench and the CPU, the problem is between the CPU and the
CTRIO itself. Communication across the backplane is failing. Here are
some known causes of this:
* - Revision meaning: "7F" means: "7" is bare board revision. "F" the revision of the assembly drawing that we are using to build the boards.
If you have older EBC, PBC or WinPLC hardware, you have two options to get them updated:
- RMA them back to Automation Direct (a part will be shipped immediately to you).
- Send them to Host Engineering (you will have to wait on the part to be modified and shipped back).
PBC FAQ0005
03-Oct-2002
Q: Are there any plans to make a Profibus Slave module for the
DL405 PLCs?
A: No, there are no plans for Host Engineering to do this.
Currently the only Profibus Slave Modules we have are the H0-PSCM;
H2-PBC and T1H-PBC. No H4-PBC nor H4-PSCM are planned.
PBC FAQ0006 (see
also CTRIO FAQ0039; EBC FAQ0038)
27-Aug-2002
Q: In order to use the newer T1H-CTRIO or H4-CTRIO, what are the
requirements as far as configuration software, hardware and
firmware?
A: Here are the requirements:
PBC FAQ0007 (see
also EBC FAQ0041; WinPLC FAQ0015)
09-Oct-2002
Q: Which H2-EBC, H2-PBC and H2-WPLC work in the newer DL205 "-1"
bases?
A: The following states the hardware revision requirements for
using these products in the newer DL205 "-1" bases (the ones that have
the local expansion I/O connector on the right side):
Find the hardware revision number on a label on the right side of the PCB (printed circuit board) as shown:
PBC FAQ0008 (see
also CTRIO FAQ0043; EBC FAQ0043)
11-Oct-2002
Q: How many T1H-CTRIOs can be installed in one base?
A: For T1H-EBC, 13. For T1H-PBC, 2. The limit is data budget.
PBC FAQ0009 (see
also CTRIO FAQ0046; EBC FAQ0047; ECOM FAQ0036; EDRV FAQ0009; ERM
FAQ0030; EZ Ethernet FAQ0018; PSCM FAQ0001; WinPLC FAQ0018; NetEdit
FAQ0014)
07-Nov-2002
Q: What software tool do I use to upgrade/downgrade my Host
Engineering hardware?
A: Refer to the following:
Host Hardware | Part Number | Firmware/Booter Upgrade Tool |
CTRIO | H0-CTRIO H2-CTRIO H4-CTRIO |
CTRIO Workbench |
EBC EBC100 |
H2-EBC H4-EBC T1H-EBC |
NetEdit3 |
T1H-EBC100 | NetEdit3 (v3.4 or higher) | |
H2-EBC100 | NetEdit3 (v3.5 or higher) | |
ECOM ECOM100 |
H0-ECOM H2-ECOM H4-ECOM |
NetEdit3 |
H0-ECOM100 H2-ECOM100 H4-ECOM100 |
NetEdit3 (v3.5 or higher) | |
EDRV | EDRV | NetEdit3 |
ERM | H2-ERM H4-ERM |
NetEdit3 or ERM Workbench |
EZ Ethernet | EZ
Ethernet EZ EtherPLUS |
EZ Touch |
PBC | H2-PBC | NetEdit3 |
PSCM | H0-PSCM H2-PSCM |
|
WinPLC | WinPLC | WinPLC Workbench |
NOTE: All the firmware for the above products can be downloaded using NetEdit3's File --> Live Update... The firmware files are stored in c:\HAPTools\Images folder.
PBC FAQ0010
10-Nov-2004
Q: Can the PBC be configured to turn all its outputs off when
communication with its Profibus master are lost?
A: Yes, this is the default behavior for all Profibus slaves. However,
the setting is done via the configuration software of the particular
Profibus master hardware being used with the PBC.
PBC FAQ0011
10-May-2007
Q: How many T1F-16AD-1 or T1F-16AD-2 modules can be installed in one
T1H-PBC or H2-PBC?
A: 3 (three). The reason is that the T1F-16AD module is a 16-channel
analog input, but each channel occupies a double-word. Therefore:
16 channels x 1 double word = 32 words
32 words x 2 bytes per word = 64 bytes
Thus each T1F-16AD module takes 64 bytes. So if you had 4 (instead of 3) modules:
4 modules x 64 bytes = 256 bytes of input
The limitation for a Profibus telegram is 244 bytes, thus, 4 modules would not work. This limitation is not due to the T1H-PBC, but rather the Profibus telegram specification. (For example, a T1H-EBC or T1H-EBC100 (Ethernet Base Controllers) do not have this limitation).
PBC FAQ0012
30-Apr-2008
Q: Does the H2-PBC support the F2-8AD4DA-1 and F2-8AD4DA-2 modules?
A: Yes, but you will have to download at least the V0.4 GSD file
(download here:
AUTD0608.GSD).
The F2-8AD4DA-1 and F2-8AD4DA-2 modules both will appear in the H2-PBC as 8 words IN (as expected), and 8 words OUT (as not expected). The extra 4 words of OUTPUT are used as the "control words" for configuring the modules themselves. The OUTPUTs of each module are defined as shown:
F2-8AD4DA-1
Output Word 1 = Channel 1
Output Word 2 = Channel 2
Output Word 3 = Channel 3
Output Word 4 = Channel 4
Output Word 5 = Input Resolution (see pg. 15-15 of D2-ANLG-M manual)
Output Word 6 = N/A
Output Word 7 = Track & Hold (see pg. 15-15 of D2-ANLG-M manual)
Output Word 8 = N/A
F2-8AD4DA-2
Output Word 1 = Channel 1
Output Word 2 = Channel 2
Output Word 3 = Channel 3
Output Word 4 = Channel 4
Output Word 5 = Input Resolution (see pg. 16-14 of D2-ANLG-M manual)
Output Word 6 = Range Selection (see pg. 16-14 of D2-ANLG-M manual)
Output Word 7 = Track & Hold (see pg. 16-15 of D2-ANLG-M manual)
Output Word 8 = N/A
PBC FAQ0013 (see
also CTRIO FAQ0026; EBC FAQ0082; WinPLC FAQ0037)
01-Jun-2009
Q: Why are the I/O Map values not saved if using CTRIO Workbench to
talk to a CTRIO in an EBC/EBC100, WinPLC, or PBC base?
A: If the CTRIO is in any of these bases, the values entered in
the CTRIO Workbench I/O Map do not determine the
CTRIO's I/O address mapping. Something other than the CTRIO itself is
determining this mapping (see chart below). Thus the I/O Map, in these
cases, is merely a documentation function.
If you enter values in this map, they will not be saved in the CTRIO .CWB file that you might create. Thus, to remember the values, you will have to use the Report button at the bottom and then either Print a hard copy, or Save it to a .TXT file.
BASE CONTROLLER | MASTER OF THE BASE CONTROLLER | I/O MAPPING DETERMINED or SHOW BY: |
DL05 | N/A | CTRIO Workench (I/O Map) |
DL06 | ||
DL205 | ||
DL405 | ||
H*-EBC or H*-EBC100 | PC (Ethernet SDK) | H*-EBC (NetEdit --> Show Base Contents) |
PC (KepDIRECT EBC) | ||
PC (Think&Do or Entivity) | ||
H*-ERM | ERM Workbench (Configure ERM) | |
H*-EBC100 only | 3rd-party (Modbus TCP) | H*-EBC100 (NetEdit --> Show Base Contents) |
H*-ECOM100 (Modbus TCP) | ||
H2-WPLC (Think&Do or Entivity) | <N/A> | H2-WPLC (Think&Do or Entivity) |
H2-WPLC (WinCE) | H2-WPLC (3rd-party application) | |
H2-PBC | 3rd-party (Profibus Master) | 3rd-party (Profibus configurator) |
T1H-EBC or T1H-EBC100 | PC (Ethernet SDK) | T1H-EBC or T1H-EBC100 (NetEdit --> Show Base Contents) |
PC (KepDIRECT EBC) | ||
PC (Think&Do or Entivity) | ||
T1H-EBC100 only | 3rd-party (Modbus TCP) | T1H-EBC100 (NetEdit --> Show Base Contents) |
H*-ECOM100 (Modbus TCP) |
NOTE: To use the table, note what is controlling the base where the H*-CTRIO is plugged into. Then note what is controlling the base controller itself. In the last column is the device or software that either determines the I/O mapping, or at least shows it to you.
PBC FAQ0014 (see
also CTRIO FAQ0045; DirectSOFT FAQ0132; DL Plus FAQ0010; DNLoader
FAQ0011; DS Data FAQ0102; EBC FAQ0083; ECOM FAQ0084; EDRV FAQ0084; ERM
FAQ0058; EZ Ethernet FAQ0010; General FAQ0004; HA-TADP FAQ0008;
Lookout Direct FAQ0015; NetEdit FAQ0037; PSCM FAQ0003; SDK FAQ0022;
SERIO FAQ0004; WinPLC FAQ0038)
31-Dec-2009
Q: What is the export classification of your products (e.g. ECCN)
A: None of our products have an ECCN. Automation Direct sells our
products and they export EAR99 NLR (No License Required). ECCN
is Export Controlled Classification Number and none of our
products are controlled.
PBC FAQ0015 (see
also NetEdit FAQ0011; EBC FAQ0004; ECOM FAQ0034; EDRV FAQ0008; ERM
FAQ0024)
07-Jan-2015
Q: Getting various errors when attempting to update the
booter/firmware for my EBCs, ECOMs, EDRVs and ERMs.
A: First make sure you isolate the device from all other tasks (i.e.
put the PLC in the STOP mode; stop HMI; isolate from busy network
traffic). Secondly, make sure you are using the latest version of
NetEdit3 which can be downloaded for free here:
http://www.hosteng.com/SW-Products/NetEdit3.zip
Here are some common problems experienced:
PBC FAQ0016 (see
also CTRIO FAQ0082)
22-Nov-2010
Q: Cannot get CTRIO Workbench's Monitor I/O function to work with
the PBC.
A: Unfortunately, it is not possible to have this
functionality for the CTRIO in the PBC. To comply with specification,
CTRIO Workbench cannot suspend the PBC's writing/reading the CTRIO's
I/O in order to perform the function, thus it is not supported.