EBC FAQ0001
28-May-2002
Q: Can I add remote I/O connections to my EBC rack?
A: No. Instead you should use multiple EBCs for the same effect.
EBC FAQ0002
10-Jul-2002
Q: Does EBC support Modbus TCP?
A: The EBC models do not (H2-EBC; H4-EBC; T1H-EBC), but the
EBC100 models do (H2-EBC100; T1H-EBC100)
EBC FAQ0003 (see also
ERM FAQ0001)
11-Jul-2002
Q: ERM Workbench is not reporting errors when the analog output
cards in the EBC rack are missing +24Vdc supply.
A: Facts Engineering (the designer of the analog cards) says that
the cards themselves do not report errors regarding the absence of
their +24Vdc supply. Therefore the EBC doesn't see them, and
subsequently neither does the ERM or the Workbench software.
EBC FAQ0004 (see also NetEdit FAQ0011; ECOM
FAQ0034; EDRV FAQ0008; ERM FAQ0024; PBC FAQ0015)
07-Jan-2015
Q: Getting various errors when attempting to update the
booter/firmware for my EBCs, ECOMs, EDRVs and ERMs.
A: First make sure you isolate the device from all other tasks
(i.e. put the PLC in the STOP mode; stop HMI; isolate from busy
network traffic). Secondly, make sure you are using the latest version
of NetEdit3 which can be downloaded for free here:
http://www.hosteng.com/SW-Products/NetEdit3.zip
Here are some common problems experienced:
EBC FAQ0005
06-Jan-2003
Q: When attempting to update the firmware for an H2-EBC, get
"Error 206 - Open file error."
A: This error is displayed when the program can't find the name
of the .bin file that was entered on the command line. This is usually
due to typing in the name of the .bin file incorrectly. Correct the
filename, or . .
Download the ERM Workbench software and use it to update the booter
and firmware of the EBC.
EBC FAQ0006 (see also
NetEdit FAQ0003, ERM FAQ0003, EDRIVE FAQ0004)
09-Sep-2009
Q: NetEdit sees ERM, EBC and EDRV, but ERM Workbench gets error
"ERM not found" when trying to write the configuration to the ERM.
A: Downloading the latest version of ERM Workbench may remedy
this problem; especially if you are using the ERM Workbench Wizard.
You should download at least ERM Workbench v1.1 Build 26. Otherwise
here are some things to try:
EBC FAQ0007 (see also
ERM FAQ0004)
07-Jan-2003
Q: Can an EBC's (hooked to an ERM) serial port be used for HMI
devices?
A: No, ERM doesn't support serial-port comm on the EBC. ERM100
& EBC100's will have serial port support, however.
EBC FAQ0008 (see also
DL Plus FAQ0001)
14-Jan-2003
Q: Can DL Plus software talk directly to EBCs?
A: DL Plus only allows Lookout to talk directly to ECOMs.
However, since Lookout has an OPC Client, it could talk directly to
KEPDirect EBC I/O Server software which talks directly to EBCs.
EBC FAQ0009
21-Jan-2003
Q: Is the KEPDirect software TCP/IP or UDP/IP?
A: UDP/IP, because the EBC only talks UDP/IP.
EBC FAQ0010 (see also
ERM FAQ0005, WinPLC FAQ0001)
22-Jan-2003
Q: Does the WinPLC allow for an ERM?
A: Yes. The WinCE-only version can have up to 6 ERMs (due to
power budget limitations) and each ERM supporting as many as 16 EBCs.
However if the WinPLC you are using is a Think&Do version you are
limited to only 1 ERM and that ERM can only have 1 EBC.
EBC FAQ0011 (see also
ERM FAQ0006)
21-Jan-2003
Q: Have DL260 using 2 ERMs on 2 separate networks. Worked for a
season. Now the second ERM fails if more than 2 EBCs are hooked to
it.
A: Since the system worked good for a while, then something
obviously changed. Check network hardware (like hubs).
EBC FAQ0012 (see also
ERM FAQ0007, SDK FAQ0001)
29-Jan-2003
Q: How do you determine what state the outputs will go to if comm
is lost on the EBC?
A: If using the SDK, this can be set with the subroutine
HEIWriteSetupData. If using ERM WorkBench the watchdog has a timeout
value and by default it is set to freeze outputs if comm is lost..
However, you can also set it to disable all outputs if watchdog fires.
EBC FAQ0013 (see also
ERM FAQ0008)
11-Jun-2002
Q: Error codes for ERM and EBC are hard to understand and
incomplete.
A: Error codes have been added to the ERM Workbench and the ERM
manual with explanations of possible causes.
EBC FAQ0014 (see also
CTRIO FAQ0012, PBC FAQ0004, WinPLC FAQ0003)
06-Feb-2003
Q: CTRIO Workbench indicates that the CTRIO module is in "Startup"
mode and all of the configuration parameters are grayed out.
A: "Startup" mode indicates that CTRIO Workbench cannot
successfully communicate with the CTRIO. The problem is not between
CTRIO Workbench and the CPU, the problem is between the CPU and the
CTRIO itself. Communication across the backplane is failing. Here are
some known causes of this:
* - Revision meaning: "7F" means: "7" is bare board revision. "F" the revision of the assembly drawing that we are using to build the boards.
If you have older EBC, PBC or WinPLC hardware, you have two options to get them updated:
- RMA them back to Automation Direct (a part will be shipped immediately to you).
- Send them to Host Engineering (you will have to wait on the part to be modified and shipped back).
EBC FAQ0015 (see also
HA-TADP FAQ0001; EDRIVE FAQ0001; ECOM FAQ0008; ERM FAQ0009; WinPLC
FAQ0004; EZ Ethernet FAQ0011)
07-Feb-2003
Q: Can the MAC address be changed?
A: The MAC address is burned into the ROM of the device and is
set just before it leaves the factory. There is no logical way for any
protocol to change this address. Host Engineering’s range for Ethernet
MAC addresses is 00.E0.62.xx.xx.xx.
However, there was a bug with the old Ether32.EXE program that could change the MAC Address! If you use Ether32.EXE to update the booter using TCP/IP protocol (i.e. use the "/pi" option on the command line), then the MAC Address could be changed by accident!
EBC FAQ0016 (see also ERM FAQ0010; ECOM FAQ0009;
EDRIVE FAQ0002)
07-Nov-2012
Q: Can ERM Workbench be used to upgrade firmware on other Host
Ethernet devices (e.g. an ECOM)? And if so, how?
A: Older
versions of ERM Workbench (before v2.0) can be used in this manner. If
ERM Workbench is v2.0 or later, then this is not possible; instead NetEdit3 must be used.
If using ERM Workbench earlier than v2.0:
EBC FAQ0017 (see also
ERM FAQ0011)
19-Feb-2003
Q: What is the response time of an EBC?
A: This is a common question and has a very technical answer. It
is also a bit ambiguous because in any system that utilizes an EBC
there are several different asynchronous loops going on that
contribute to overall delay (or response time). What follows are 14
formulas for calculating worse-case response time for all module types
(Discrete IN, Discrete OUT, Analog IN, Analog OUT). Keep in mind, this
is not a scan time that you are calculating, but rather a response
time.
A scan time is generally a constant (like that of a PLC). Since there are several asynchronous things happening in any EBC system, there is no such thing as a constant scan time.
A response time calculation will, however, give you the worse-case time possible depending on whether you want to know:
Use the following table to figure out which FORMULAs to use for your particular application. Add the total time from each of the FORMULAs you must use, and you will have a worse-case response time.
FORMULA | ||||||||||||||||
MASTER | SLAVE | I/O TYPE | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 |
PC | H2-EBC | Discrete I/O | Y | Y | Y | |||||||||||
Analog IN | Y | Y | Y | Y | Y | |||||||||||
Analog OUT | Y | Y | Y | Y | Y | |||||||||||
H2-EBC100 | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | Y | |||||||||||
Analog OUT | Y | Y | Y | Y | Y | |||||||||||
H4-EBC | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | Y | |||||||||||
Analog OUT | Y | Y | Y | Y | Y | |||||||||||
T1H-EBC | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | ||||||||||||
Analog OUT | Y | Y | Y | Y | ||||||||||||
T1H-EBC100 | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | ||||||||||||
Analog OUT | Y | Y | Y | Y | ||||||||||||
ERM | H2-EBC | Discrete I/O | Y | Y | Y | |||||||||||
Analog IN | Y | Y | Y | Y | Y | |||||||||||
Analog OUT | Y | Y | Y | Y | Y | |||||||||||
H2-EBC100 | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | Y | |||||||||||
Analog OUT | Y | Y | Y | Y | Y | |||||||||||
H4-EBC | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | Y | |||||||||||
Analog OUT | Y | Y | Y | Y | Y | |||||||||||
T1H-EBC | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | ||||||||||||
Analog OUT | Y | Y | Y | Y | ||||||||||||
T1H-EBC100 | Discrete I/O | Y | Y | Y | ||||||||||||
Analog IN | Y | Y | Y | Y | ||||||||||||
Analog OUT | Y | Y | Y | Y |
FORMULAs:
Time(1) = Scan time of application
Time(2) = PLCScanTime x 4 (or 3)
Time(3) = Microseconds
Time(4) = 2ms x #ofEBCs
Time(5) = 2ms x Total#ofAIChForBase
Time(6) = 2ms x Total#ofAOChForBase
Time(7) = Specified for particular module
For
AI it is generally called "Data Acquisition Time"
For
AO it is generally called "Conversion Setting Time"
Time(8) = 1ms + (1ms x
Total#of8ChAOModsForBase) + (1.5ms x Total#of16ChAOModsForBase)
Time(9) = 1ms
Time(10) = 1ms x #ofH2EBC100s
Time(11) = 2ms + (0.5ms x #ofAIChsOfMod)
Time(12) = 2ms + (0.5ms x #ofAOChsOfMod)
Time(13) = 0.7ms
Time(14) = 0.7ms + (0.7ms x
Total#of8ChAOModsForBase) + (1ms x Total#of16ChAOModsForBase)
FORMULA DESCRIPTIONS
Time(1) = Scan time of application
If the controlling device is a PC, then the execution time of the application code must first be considered. In some applications this can be a considerable amount of time (in the millisecond range).
Time(2) = PLCScanTime x 4 (or 3)
If the controlling device is an H2-ERM or H4-ERM, then you must consider the scan time of the PLC. There are 4 data types the ERM has to process:
- Discrete inputs (bit ins)
- Discrete outputs (bit outs)
- Analog inputs (word ins)
- Analog outputs (word outs)
The DL PLCs can only process one type of data per PLC scan. There are always "bit ins, bit outs and word ins" simply because the ERM's error bits and status information are written and read even if there are no modules installed in the slaved EBC. But since the PLC only processes one type of data per PLC scan it takes at least 3 PLC scans (e.g. bit in, bit out, word in) to process the types. Of course if you have analog output modules (word outs) then it would take 4 PLC scans.
Time(3) = Microseconds
Next, the time on the Ethernet wire for the PC to talk to the EBC, or the ERM to talk to the EBC is negligible. At a transmission rate of 10 Mbps (or especially 100Mbps) there is really so little data (by comparison), that this time is not considered unless you have a non-isolated busy network.
Time(4) = 2ms x #ofEBCs
The H2-EBCs and H4-EBCs have an image registers that their masters (i.e. a PC or an ERM) talk to. It takes 2 ms to read or write data to these registers and get an acknowledgment back. Even when figuring response time (which is what we are doing), all the EBCs connected to the master are going to contribute to delay in getting a change to an output, or reading a change from an input in the EBC you are interested in simply because the master has to poll all the slaves in his list. And this takes time. Thus it takes 2 ms times the number of EBCs in the network that this particular master is talking to. When considering Discrete I/O, there is essentially no more delay added to this time.
Time(5) = 2ms x Total#ofAIChForBase
The H2-EBC and H4-EBCs are continually updating their image registers with the data from all analog input (AI) modules. Even though there are 4 data types the only ones that really have any affect on response time are the analogs (word in, word out). The maximum time it could take the EBC to read a new value from an analog input module is 2 ms per channel. But this delay is increased as more analog input channels are added to the base. The more analog input channels in the base, the slower the over all response of all analog input channels in the base. Please note that this has to do with the total number of analog input channels, not analog input modules.
Time(6) = 2ms x Total#ofAOChForBase
The H2-EBC and H4-EBCs are continually updating their analog output (AO) modules with the data from their image registers. Even though there are 4 data types the only ones that really have any affect on response time are the analogs (word in, word out). The maximum time it could take the EBC to write a new value to an analog output module is 2 ms per channel. But this delay is increased as more analog output channels are added to the base. The more analog output channels in the base, the slower the over all response of all analog output channels in the base. Please note that this has to do with the total number of analog output channels, not analog output modules.
Time(7) = Specified for particular module
For AI it is generally called "Data Acquisition Time"
For AO it is generally called "Conversion Setting Time"The time it takes to see a change from a particular analog input channel until it actually shows up as data on the EBC bus is specified as the "Data Acquisition Time" of that particular module and can be found in its specs. Likewise the time it takes for the data on the bus to show up as a change in the output of the analog output channel is called "Conversion Setting Time" or sometimes just "Conversion Time" and can be found in its specs.
Time(8) = 1ms + (1ms x Total#of8ChAOModsForBase) + (1.5ms x Total#of16ChAOModsForBase)
The T1H-EBC has an image register that its master (i.e. a PC or an ERM) talks to. It normally takes 1 ms to read or write data to this register and get an acknowledgment back. However, unlike the H2-EBC or the H4-EBC it is not fixed. Instead it is so fast that whereas the H2-EBC and the H4-EBC delays divide up into a "read/write time" and an "analog in/analog out" time using formulas (4), (5) and (6) above, the T1H-EBC combines them into one thing; "read/write & analog). This 1 ms delay is increased slightly if you have analog outputs installed in the EBC. What happens is when a write is performed to an analog output in the EBC, the normal scan is interrupted and the EBC immediately writes the data to the analog output module. So for each 8-channel analog output module, you add an additional 1 ms of delay. For each 16-channel analog output module you add 1.5 ms. Reading analog inputs, however, is so fast it is negligible. Please note that this has to do with the total number of analog output modules in the base, not analog output channels (opposite of H2-EBC and H4-EBC).
Time(9) = 1ms
The T1H-EBC has an image register that its master (i.e. a PC or an ERM) talks to. It normally takes 1 ms to read or write data to this register and get an acknowledgment back. However, unlike the H2-EBC or the H4-EBC it is not fixed. Instead it is so fast that whereas the H2-EBC and the H4-EBC delays divide up into a "read/write time" and an "analog in/analog out" time using formulas (4), (5) and (6) above, the T1H-EBC combines them into one thing; "read/write & analog." This 1 ms delay is increased slightly if you have analog outputs installed in the EBC. However, when reading analog inputs, it is so fast it is negligible, so no additional time is added to the 1 ms as in formula (8) above.
Time(10) = 1ms x #ofH2EBC100s
Like the H2-EBCs and H4-EBCs, the H2-EBC100s have an image registers that their masters (i.e. a PC or an ERM) talk to. Because of the faster processor in the H2-EBC100 it only takes 1ms to read or write data to these registers and get an acknowledgment back. (i.e. the decrease in read/write time is not significantly improved by the 100Mbps VS the 10Mbps, but rather the faster processor in the H2-EBC100 itself). Even when figuring response time (which is what we are doing), all the H2-EBC100s connected to the master are going to contribute to delay in getting a change to an output, or reading a change from an input in the H2-EBC100 you are interested in simply because the master has to poll all the slaves in his list. And this takes time. Thus it takes 1 ms times the number of H2-EBC100s in the network that this particular master is talking to. When considering Discrete I/O, there is essentially no more delay added to this time.
Time(11) = 2ms + (0.5ms x #ofAIChsOfMod)
Like the H2-EBCs and H4-EBCs the H2-EBC100s are continually updating their image registers with the data from all analog input (AI) modules. Even though there are 4 data types the only ones that really have any affect on response time are the analogs (word in, word out). The maximum time it could take the H2-EBC100 to read a new value from an analog input module is 0.5 ms times the number of channels that particular analog input module has enabled plus an inherent delay of 2 ms for the module itself. Unlike the H2-EBC and H4-EBC analog input reads, this delay is not increased as more analog input channels are added to the base. In other words if more analog input channels are added to the base, this will not affect the over all response of any other analog input channels in the base. This essentially means that the newer H2-EBC100 is running each analog input module in its base in parallel with the others! Great feature, eh?
Time(12) = 2ms + (0.5ms x #ofAOChsOfMod)
Like the H2-EBCs and H4-EBCs the H2-EBC100s are continually updating their analog output (AO) modules with the data from their image registers. Even though there are 4 data types the only ones that really have any affect on response time are the analogs (word in, word out). The maximum time it could take the H2-EBC100 to write a new value to an analog output module is 0.5 ms times the number of channels that particular analog output module has enabled plus an inherent delay of 2 ms for the module itself. Unlike the H2-EBC and H4-EBC analog output writes, this delay is not increased as more analog output channels are added to the base. In other words if more analog output channels are added to the base, this will not affect the over all response of any other analog output channels in the base. This essentially means that the newer H2-EBC100 is running each analog output module in its base in parallel with the others! Great feature, eh?
Time(13) = 0.7ms
Like the T1H-EBC the T1H-EBC100 has an image register that its master (i.e. a PC or an ERM) talks to. It normally takes 0.7 ms to read or write data to this register and get an acknowledgment back. However, unlike the H2-EBC or the H4-EBC it is not fixed. Instead it is so fast that whereas the H2-EBC and the H4-EBC delays divide up into a "read/write time" and an "analog in/analog out" time using formulas (4), (5) and (6) above, the T1H-EBC100 combines them into one thing; "read/write & analog." This 0.7 ms delay is increased slightly if you have analog outputs installed in the EBC. However, when reading analog inputs, it is so fast it is negligible, so no additional time is added to the 0.7 ms as in formula (8) above.
Time(14) = 0.7ms + (0.7ms x Total#of8ChAOModsForBase) + (1ms x Total#of16ChAOModsForBase)
Like the T1H-EBC the T1H-EBC100 has an image register that its master (i.e. a PC or an ERM) talks to. It normally takes 0.7 ms to read or write data to this register and get an acknowledgment back. However, unlike the H2-EBC or the H4-EBC it is not fixed. Instead it is so fast that whereas the H2-EBC and the H4-EBC delays divide up into a "read/write time" and an "analog in/analog out" time using formulas (4), (5) and (6) above, the T1H-EBC100 combines them into one thing; "read/write & analog." This 0.7 ms delay is increased slightly if you have analog outputs installed in the T1H-EBC100. What happens is when a write is performed to an analog output in the T1H-EBC100, the normal scan is interrupted and the T1H-EBC100 immediately writes the data to the analog output module. So for each 8-channel analog output module, you add an additional 0.7 ms of delay. For each 16-channel analog output module you add 1 ms. Reading analog inputs, however, is so fast it is negligible. Please note that this has to do with the total number of analog output modules in the base, not analog output channels (opposite of H2-EBC and H4-EBC).
A Final Word
With the above 14 formulas you can calculate worse-case response times for as many pieces in your particular application as you desire. Of course statistics teach us that the typical time will generally be about half of worse case.
THREE EXAMPLES
(1) Using H2-ERM and H2-EBC
Lets say we have a PLC with a scan time of 20 ms, an H2-ERM, two H2-EBCs and the EBC we are interested in has one 8-channel analog output (F2-08DA-2), and one 8-channel analog input (F2-08AD-1). The network is isolated.
First let's calculate the response time from the PLC to a signal change on the analog output module. According to the above chart I would use FORMULAs 2, 3, 4, 6 & 7, thus:
Time(2) = PLCScanTime x 4 (or 3) = 20 x 4 = 80 ms (multiply by 4 because we have all 4 data types in the EBC base)
Time(3) = Microseconds = 0 ms (this is negligible)
Time(4) = 2ms x #ofEBCs = 2 x 2 = 4 ms (two EBCs on the network)
Time(6) = 2ms x Total#ofAOChForBase = 2 x 8 = 16 ms
Time(7) = "Conversion Setting Time" for AO = 9 ms (as specified for the F2-08DA-2)Thus the response time from PLC to signal change on analog output = 80 + 0 + 4 + 16 + 9 = 109 ms (worse case)
Next let's calculate the response time from a change on the analog input signal to the PLC data. According to the above chart I would use FORMULAs 2, 3, 4, 5 & 7, thus:
Time(2) = PLCScanTime x 4 (or 3) = 20 x 4 = 80 ms (same as above)
Time(3) = Microseconds = 0 ms (same as above)
Time(4) = 2ms x #ofEBCs = 2 x 2 = 4 ms (same as above)
Time(5) = 2ms x Total#ofAIChForBase = 2 x 8 = 16 ms
Time(7) = "Data Acquisition Time" for AI = 3 ms/channel = 3 x 8 = 24 ms (as specified for the F2-08AD-1)Thus the response time from signal change on analog input to PLC = 80 + 0 + 4 + 16 + 24 = 124 ms (worse case)
(2) Using H2-ERM and H2-EBC100
Lets try the same thing as above, only instead of H2-EBCs we replace them with H2-EBC100s.
First let's calculate the response time from the PLC to a signal change on the analog output module. According to the above chart I would use FORMULAs 2, 3, 7, 10 & 12 thus:
Time(2) = PLCScanTime x 4 (or 3) = 20 x 4 = 80 ms (multiply by 4 because we have all 4 data types in the EBC base)
Time(3) = Microseconds = 0 ms (this is negligible)
Time(7) = "Conversion Setting Time" for AO = 9 ms (as specified for the F2-08DA-2)
Time(10) = 1ms x #ofH2EBC100s = 1 x 2 = 2 ms (two EBC100s on the network)
Time(12) = 2ms + (0.5ms x #ofAOChsOfMod) = 2 + (0.5 x 8) = 2 + 4 = 6 msThus the response time from PLC to signal change on analog output = 80 + 0 + 9 + 2 + 6 = 97 ms (worse case)
Next let's calculate the response time from a change on the analog input signal to the PLC data. According to the above chart I would use FORMULAs 2, 3, 7, 10 & 11 thus:
Time(2) = PLCScanTime x 4 (or 3) = 20 x 4 = 80 ms (same as above)
Time(3) = Microseconds = 0 ms (same as above)
Time(7) = "Data Acquisition Time" for AI = 3 ms/channel = 3 x 8 = 24 ms (as specified for the F2-08AD-1)
Time(10) = 1ms x #ofH2EBC100s = 1 x 2 = 2 ms (same as above)
Time(11) = 2ms + (0.5ms x #ofAIChsOfMod) = 2 + (0.5 x 8) = 2 + 4 = 6 msThus the response time from signal change on analog input to PLC = 80 + 0 + 24 + 2 + 6 = 112 ms (worse case)
So you can see that replacing the H2-EBC with the H2-EBC100 improved the response time in both directions.
(3) Using H2-ERM and T1H-EBC
Lets say we have a PLC with a scan time of 20 ms, an H2-ERM, a T1H-EBC which has one 8-channel analog output (T1F-08DA-2), and two 8-channel analog inputs (T1F-08AD-1). The network is isolated.
First let's calculate the response time from the PLC to a signal change on the analog output module. According to the above chart I would use FORMULAs 2, 3, 7 & 8 thus:
Time(2) = PLCScanTime x 4 (or 3) = 20 x 4 = 80 ms (multiply by 4 because we have all 4 data types in the EBC base)
Time(3) = Microseconds = 0 ms (this is negligible)
Time(7) = "Conversion Setting Time" for AO = 0.1 ms (as specified for the T1F-08DA-2)
Time(8) = 1ms + (1ms x Total#of8ChAOModsForBase) + (1.5ms x Total#of16ChAOModsForBase) = 1 + (1 x 1) + (1.5 x 0) = 1 + 1 + 0 = 2 msThus the response time from PLC to signal change on analog output = 80 + 0 + 0.1 + 2 = 82.1 ms (worse case)
Next let's calculate the response time from a change on the analog input signal to the PLC data. According to the above chart I would use FORMULAs 2, 3, 7 & thus:
Time(2) = PLCScanTime x 4 (or 3) = 20 x 4 = 80 ms (same as above)
Time(3) = Microseconds = 0 ms (same as above)
Time(7) = "Data Acquisition Time" for AI = 5 ms/channel = 5 x 8 = 40 ms (as specified for the T1F-08AD-1)
Time(9) = 1msThus the response time from signal change on analog input to PLC = 80 + 0 + 40 + 1 = 121 ms (worse case)
EBC FAQ0018
27-Feb-2003
Q: Will Wonderware's 205/405 EBC driver work with the T1H-EBC?
A: No. Their original driver will not work with the T1H-EBC. Must
have an updated driver for this to work. Check with Wonderware to see
if they have updated their driver to support T1H-EBC.
EBC FAQ0019
27-Feb-2003
Q: T1H-EBC shows up in NetEdit with a Name and Description as
"???EBC" but in ERM Workbench it is "Term EBC."
A: The default Name and Description for the T1H-EBC is "???EBC,"
but this can be changed with NetEdit.
EBC FAQ0020
26-Feb-2003
Q: Need to update the booter/firmware for EBC. Where can I obtain
the latest booter/firmware files?
A: This is done automatically using the Live Update feature of
NetEdit3.
The latest booter/firmware files (.BIN) are then loaded onto your PC in the HAPTools\Images folders. Now you can use NetEdit3 to update your booter/firmware.
EBC FAQ0021
28-Feb-2003
Q: Can I use Wonderware's InControl software to control a
DirectLogic rack of I/O?
A: Yes. Wonderware makes a driver that will talk directly to our
H2-EBC and H4-EBC. You will have to go to the Wonderware website and
search for it (http://www.wonderware.com)
or call them and order it.
EBC FAQ0022 (see also
ERM FAQ0012)
06-Mar-2003
Q: Is there any advantage of using a switch over a hub with
ERM/EBC network?
A: Since the ERM/EBC network is supposed to be dedicated, then
the answer is "no."
However, if the ERM/EBC are on a network that has other devices (not advisable!) then of course, one may prove to be more advantageous given the scenario. A hub blindly repeats data that it hears on one port to all of its ports. Therefore only one Ethernet node connected to it can talk at a time. A switch, however, evaluates the source and destination of the Ethernet packet and can therefore learn paths. This allows many Ethernet nodes to talk to one another over private connections simultaneously through the switch. A switch would probably work out better if the ERM/EBC are on a regular office PC network (again, not advisable!)
EBC FAQ0023 (see also
ERM FAQ0014; ECOM FAQ0019; EDRIVE FAQ0005; EZ Ethernet FAQ0014)
26-Mar-2003
Q: For my Ethernet network that would exceed 100 meters, is a
standard hub considered a repeater so as to increase the permissible
length?
A: Yes. The maximum distance per 10BaseT cable segment is 100
meters. Repeaters (e.g. hubs, bridges, etc.) extend the distance. Each
cable segment attached to a repeater can be 100 meters. Thus, two
repeaters can gain you a total of 300 meters distance.
EBC FAQ0024 (see also
ERM FAQ0017; WinPLC FAQ0005)
22-Apr-2003
Q: How many EBCs can one ERM support?
A: Normally 16. But if the CPU is a Think&Do WinPLC then this
is limited to 1 (this limitation does not apply to the WinCE-only
version of the WinPLC).
EBC FAQ0025
10-Sep-2002
Q: When using H4-EBC base configuration, what is the difference
between F4-08THM vs F4-08THM Unipolar?
A: Normally the F4-08THM is used with bipolar thermocouples and
returns a 2's compliment value temperature in the range of -32768 to
+32767. However, if unipolar thermocouples are used with the F4-08THM
module and it is set up as such, then it returns a temperature in the
range of 0 to 65535. So, it is necessary for the EBC to know this so
that it will know when and when not to convert the value to 2's
compliment.
EBC FAQ0026
13-Sep-2002
Q: When attempting to update the firmware for an T1H-EBC, the LINK
GOOD and ERROR lights come on.
A: If no lights come on before seeing the LINK GOOD and then the
ERROR light comes on, then it could be a hardware problem (return for
repair) or it could be that the firmware is
corrupt.<INCOMPLETE><INCOMPLETE>
EBC FAQ0027
13-Sep-2002
Q: When attempting to update the firmware for an T1H-EBC, the
ERROR lights flashes.
A: If the ERROR light is flashing this could indicate an error
code by the number of times it flashes before a pause:
BLINKS | MEANING | REMEDY |
Rapid blinking | Operating System (OS) OK, modules removed | Check modules |
2 | No Operating System (OS) found | Load firmware |
3 | Ethernet initialization problem | If problem is persistent over power cycling, send in for repair |
4 | Invalid boot version | Upgrade booter to match what firmware requires |
EBC FAQ0028 (see also
SERIO FAQ0001; WinPLC FAQ0012)
09-Sep-2002
Q: Are there slot restrictions for the SERIO module?
A: There is no slot restriction for the H2-SERIO module.
EBC FAQ0029 (see also CTRIO FAQ0034; ERM
FAQ0019)
18-Nov-2015
Q: Will the CTRIO/CTRIO2 work in the local expansion bases of
DL205 or DL405 line?
A: No. Do not install the H4-CTRIO nor the H2-CTRIO/CTRIO2 in
local expansion. It will however work in the ERM/EBC configuration. So
you can expand the I/O using the ERM/EBC instead.
EBC FAQ0030 (see also WinPLC FAQ0013, CTRIO
FAQ0014)
17-Nov-2015
Q: What is the expected hit on the scan time for adding an
H2-CTRIO/CTRIO2 to WinPLC or EBC/EBC100 rack? When connected with
Entivity and adding more than one H2-CTRIO/CTRIO2 I get a timeout.
A: This is different for each product:
For WinPLC, there could be a detectable hit (however, small) simply because it has a comparatively slower processor (100MHz).
On the EBC/EBC100 itself, the addition of a CTRIO will probably not be noticeable at all simply because the EBC/EBC100 has only one thing to do . . . update its I/O.
On a Think&Do or Entivity application there will be about 7ms per CTRIO/CTRIO2 hit due to the number of tags that are created to handle the extra I/O scanning of the CTRIO/CTRIO2 from the PC. Thus, in the Connectivity Center of this software, under "Attributes" you must increase the "Timeout Value for Retries(ms)" value accordingly.
EBC FAQ0031
19-Sep-2002
Q: After attempting to upgrade the booter now my T1H-EBC will not
work at all.
A: The booter is definitely critical when it is being updated. In
older versions if it was corrupted during the update, there was no way
to recover and the EBC would just have to be sent back to Host
Engineering to be fixed! With the latest booter (at least v3.0.102)
you can now recover from this fatal state if trying to update later
versions. However, if your EBC will now no longer function (won't
accept booter nor firmware) then it must be shipped to Host
Engineering for repair. The latest booter is always included in the
firmware download ZIP file on our website.
EBC FAQ0032
19-Sep-2002
Q: Unable to see any of the THM, RTD or 08AD-1 modules in H2-EBC,
H4-EBC and T1H-EBCs.
A: This is due to the THM, RTD and 08AD-1 modules powering up with
the broken-transmitter bits turned on (before they are actually
checked). We compensated the problem in our latest firmware for all
EBCs. Must have at least EBC firmware v2.1.296.
EBC FAQ0033 (see also
ECOM 0028; ERM FAQ0020, EDRV FAQ0007, EZ Ethernet FAQ0017; DirectSOFT
FAQ0181; DS Data FAQ0088; SDK FAQ0012; NetEdit FAQ0013)
20-Jul-2018
Q: What Ethernet protocols are used by your products?
A: Refer to chart below:
Product | Ethernet Protocols | ||||||||||||||
UDP/IP | IPX | TCP/IP | Raw Ethernet Broadcast (1) | ||||||||||||
K-seq | DirectNet | ECOM (2) | Koyo Backplane | User Defined Data | Proprietary (1) | K-seq | DirectNet | ECOM (2) | Proprietary (1) | Modbus TCP Master | Modbus TCP Slave | Proprietary (1) | Koyo Backplane | ||
Hardware | ECOM | Y | Y | Y | Y (3) | Y (4) | Y | Y | Y | Y (5) | |||||
ECOM100 | Y | Y | Y | Y (3) | Y (4) | Y | Y | Y | Y (6) | Y | Y (5) | ||||
EBC | Y | Y | |||||||||||||
EBC100 | Y | Y | Y | ||||||||||||
ERM | Y (7) | Y (7) | (8) | ||||||||||||
EDRV | Y | Y | Y (12) | ||||||||||||
EZ Ethernet | Y | Y | Y | Y | Y | Y | |||||||||
EZ EtherPLUS | Y | Y | Y | Y | Y | Y | Y | ||||||||
WinPLC | Y | ||||||||||||||
Software | DirectSOFT | Y | Y | Y | Y | Y | Y | ||||||||
DS Data | Y | Y | Y | Y | Y | Y | |||||||||
Ethernet SDK | Y (9) | Y | Y | Y (9) | Y | Y | |||||||||
NetEdit | Y (10) | Y (11) | Y (10) | Y (11) |
(1)
Not an industry standard. However, protocol is available for 3rd-party
development upon request.
(2) Not really a distinct protocol. This setting is used
to intelligently pick K-sequence or DirectNet as needed by the
hardware/software.
(3) Used when doing ECOM-to-ECOM via RX/WX instructions
with RX/WX Node Map configured in sending ECOM.
(4) Used when doing ECOM-to-PC (Report-by-Exception) via
RX/WX instructions (Address 90 only) with ECOM's dipswitch 7 set ON.
(5) Used when doing ECOM-to-ECOM via RX/WX instructions
without RX/WX Node Map configured in sending ECOM.
(6) RX/WX Node Map must be configured in ECOM.
(7) ERM can talk to one slave with UDP/IP and another
with IPX simultaneously.
(8) No longer in planning (i.e.
canceled).
(9) Requires K-sequence protocol spec (request from
Automation Direct)
(10) Uses K-sequence to perform "Test CPU Access!"
function.
(11) Uses this protocol to perform "Show Base
Contents..." function.
(12) The older HA-EDRV2 cannot talk Modbus TCP.
EBC FAQ0034 (see also
ERM FAQ0021, WinPLC FAQ0014)
05-Feb-2008
Q: After writing configuration to ERM and EBC get "Error 228 -
Backplane error."
A: Error 228 is defined as "Backplane read/write request queue
full" and it means that for some reason the CPU is either rejecting
requests from its ERM or not accepting them. Common causes:
EBC FAQ0035
05-Dec-2003
Q: Do you make or recommend any wireless Ethernet devices that
could be used with or actually replace the EBC?
A: No, but if you bought standard wireless Ethernet switches/hubs,
the EBC should work with those. However, you may have to increase the
timeout and retry values due to the wireless configuration.
EBC FAQ0036 (see also
NetEdit FAQ0008)
26-Sep-2002
Q: Using NetEdit to configure an H4-EBC, but the F4-16DA-2 is not
listed as an option to put in the slots.
A: You can choose one of two things:
EBC FAQ0037
27-Sep-2002
Q: The EBC ERR light comes on when Think&Do is in the RUN mode,
but not when it is in the I/O View.
A: This is due to the increase in the scan time in the RUN mode.
The I/O View scan time is much quicker than the RUN mode. Therefore
you must use Think&Do to increase the EBC timeouts and perhaps
even the Retries value as well.
EBC FAQ0038 (see also
CTRIO FAQ0039; PBC FAQ0006)
27-Aug-2002
Q: In order to use the newer T1H-CTRIO or H4-CTRIO, what are the
requirements as far as configuration software, hardware and
firmware?
A: Here are the requirements:
EBC FAQ0039 (see also
ERM FAQ0022)
08-Oct-2002
Q: Using H4-ERM to H4-EBC. Does this configuration support the use
of D4-EX local I/O expansion modules off of the H4-EBC?
A: Yes. The H4-ERM can have up to 16 H4-EBC slaves. On each H4-EBC
it is possible to utilize the D4-EX local I/O expansion to attach 3
more 405 bases. Thus that is 16 x 4 = 64 total 405 bases of I/O
attached to one ERM!
EBC FAQ0040 (see also
ERM FAQ0023)
08-Oct-2002
Q: Using H2-ERM to H2-EBC. Does this configuration support the use
of D2-EM/CM local I/O expansion modules off of the H2-EBC?
A: No. H2-EBC does not support the local I/O expansion of the
DL250-1/260 variety. But the solution is to just use another H2-EBC
instead of using the D2-EM/CM pair.
EBC FAQ0041 (see also
PBC FAQ0007; WinPLC FAQ0015)
09-Oct-2002
Q: Which H2-EBC, H2-PBC and H2-WPLC work in the newer DL205 "-1"
bases?
A: The following states the hardware revision requirements for
using these products in the newer DL205 "-1" bases (the ones that have
the local expansion I/O connector on the right side):
Find the hardware revision number on a label on the right side of the PCB (printed circuit board) as shown:
EBC FAQ0042 (see also
ERM FAQ0025; SDK FAQ0006)
07-Oct-2002
Q: My EBC outputs sometimes go OFF intermittently; at the same time
the Error light on the EBC comes on.
A: When the Error light comes ON, this indicates that the watchdog
circuit in the EBC has fired. By default the EBC's watchdog is set to
250ms. This means that if the EBC doesn't get a communication from its
master (e.g. ERM; Entivity; Ethernet SDK app; KEPDirect; etc.) within
250ms then it will fire. When the watchdog fires the outputs in the
EBC base will all be switched OFF for safety purposes. The watchdog
time can be set via the master configuration software (e.g. ERM
Workbench; Entivity; etc.). It can also be disabled. If the watchdog
is disabled then the outputs in the EBC base will simply freeze to
their last state before the watchdog fired.
Thus in the case above where the outputs appear to go OFF intermittently, this is probably due to the watchdog time being too small for the application scan time. So either disable the watchdog totally (NOT RECOMMENDED FOR SAFETY REASONS), or adjust the time to a higher value.
EBC FAQ0043 (see also
CTRIO FAQ0043; PBC FAQ0008)
11-Oct-2002
Q: How many T1H-CTRIOs can be installed in one base?
A: For T1H-EBC, 13. For T1H-PBC, 2. The limit is data budget.
EBC FAQ0044
14-Oct-2002
Q: Using the local expansion I/O from an H4-EBC. Is there a bit in
the EBC that indicates when the local expansion I/O has been
disconnected?
A: No. Either:
EBC FAQ0045
21-Oct-2002
Q: How many modules can be installed in the T1H-EBC?
A: The limit is 16 modules (digital and/or analog). However, in
the past we have found that there are certain apparently random
combinations of 16 modules that do not function properly. When this
occurs usually the T1H-EBC is unable to see the module(s) at the end
of the configuration. So far we have not been able to nail down
exactly the rhyme or reason behind such failures but we are sure it
has to do with backplane impedance. Fortunately this is a very rare
thing. If this happens with your configuration, try a few of the
following suggestions:
EBC FAQ0046 (see also
ERM FAQ0029)
25-Oct-2002
Q: Can an EBC support an ERM in its base?
A: No. The only things that can support ERMs are a regular DL PLC
or a WinPLC.
EBC FAQ0047 (see also Do-more
FAQ0038; CTRIO FAQ0046; ECOM FAQ0036; EDRV FAQ0009; ERM FAQ0030;
EZ Ethernet FAQ0018; PBC FAQ0009; PSCM FAQ0001; WinPLC FAQ0018;
NetEdit FAQ0014; MB-GATEWAY FAQ0003)
13-Dec-2017
Q: What software tool do I use to upgrade/downgrade my Host
Engineering hardware?
A: Refer to the following:
Host Hardware | Part Number | Firmware/Booter Upgrade Tool |
CTRIO CTRIO2 |
H0-CTRIO H4-CTRIO H0-CTRIO2 |
CTRIO
Workbench |
H2-CTRIO
T1H-CTRIO H2-CTRIO2 T1H-CTRIO2 |
CTRIO
Workbench or Do-more Designer |
|
DM1 DM1E |
BX-DM1-x BX-DM1E-x H2-DM1 H2-DM1E T1H-DM1 T1H-DM1E |
Do-more Designer |
EBC EBC100 |
H2-EBC H4-EBC T1H-EBC T1H-EBC100 H2-EBC100 |
NetEdit3 |
ECOM ECOM100 |
H0-ECOM H2-ECOM H4-ECOM H0-ECOM100 H2-ECOM100 |
|
ECOMLT (POM) |
BX-P-ECOMLT | |
EDRV EDRV100 |
GS-EDRV GS-EDRV100 |
|
ERM ERM100 |
H2-ERM H4-ERM H2-ERM100 |
NetEdit3
or ERM Workbench |
EZ Ethernet | EZ
Ethernet EZ EtherPLUS |
EZ Touch |
MB-GATEWAY | MB-GATEWAY | NetEdit3 |
PBC | H2-PBC | |
PSCM |
H0-PSCM
H2-PSCM
|
|
WinPLC | WinPLC | WinPLC Workbench |
NOTE: All the firmware for the above products can be downloaded using NetEdit3's File --> Live Update... The firmware files are stored in c:\HAPTools\Images folder, or in the case of the Do-more PLCs, under the Images subfolder in the Do-more Designer's installation Bin folder.
EBC FAQ0048 (see also CTRIO FAQ0013; ERM
FAQ0031; WinPLC FAQ0029; SDK FAQ0013)
17-Nov-2015
Q: Is it possible to utilize the CTRIO System Functions everywhere
the CTRIO/CTRIO2 can be installed?
A: In firmware v2.x System Functions were added to the CTRIO
products (H0-, H2-, H4- and T1H-CTRIO) and are present in all CTRIO2
modules. These System Functions allow the writing (and reading) of
various internal registers of the CTRIO/CTRIO2. The following table
shows what scenarios that these System Functions can be used and how to
use them:
System Functions | CTRIO/CTRIO2 Installation |
|||||||||
Do-more Local Base | Do-more Ethernet I/O Base with EBC100 | DL PLC Local Base | DL PLC Local Expansion Base | DL PLC with ERM-EBC | WinPLC (Think&Do) Local Base | WinPLC (Think&Do) with ERM-EBC | Think&Do (Entivity) to EBC | Ethernet SDK to EBC | ||
Mapped System Functions | Status of Inputs | YES (1) |
YES (1) |
YES (3) |
NO (5) | YES (3) |
YES (7) |
YES (7) | YES (7) |
YES (9) |
Mode & Status of Outputs | YES (1) |
YES (1) |
YES (3) |
NO (5) | YES (3) |
YES (7) |
YES (7) |
YES (7) |
YES (9) |
|
CTRIO/CTRIO2 Shared RAM System Functions | 0x01 - Read all registers | YES (2) |
YES (2) |
YES (4) |
NO (5) | NO
(6) |
YES (8) |
YES (8) |
YES (8) |
YES (10) |
0x02 - Write all registers | YES (2) |
YES (2) |
YES (4) |
NO (5) | NO
(6) |
YES (8) |
YES (8) |
YES (8) |
YES (10) | |
0x03 - Read one register | YES (2) |
YES (2) |
YES (4) | NO (5) | NO
(6) |
YES (8) |
YES (8) |
YES (8) |
YES (10) | |
0x04 - Write one register | YES (2) |
YES (2) |
YES (4) | NO (5) | NO
(6) |
YES (8) |
YES (8) |
YES (8) |
YES (10) | |
0x05 - Write reset value | YES (2) |
YES (2) |
YES (4) | NO (5) | NO
(6) |
YES (8) |
YES (8) |
YES (8) |
YES (10) |
(1) - Mapped to the
CTRIO/CTRIO2 device structure members
(2) - Use the CTREGWR & CTREGRD instructions (can
only read/write one register at a time)
(3) - Mapped to V-memory as configured in the
CTRIO/CTRIO2 using CTRIO Workbench
(4) - Use the CTRRGWR & CTRRGRD IBox instructions
(can only read/write one register at a time)
(5) - CTRIO/CTRIO2
will not work in local expansion bases
(6) - No way to tell the ERM/ERM100 to access the
Shared RAM of CTRIO/CTRIO2 in EBC/EBC100 base
(7) - Mapped to memory as configured in Think&Do
(8) - Use Shared RAM Operations for CTRIO/CTRIO2 in a
CALL block
(9) - Mapped as shown with NetEdit3 Show Base Contents
(10) - Use HEIWriteSharedRAM & HEIReadSharedRAM
routines
EBC FAQ0049 (see also
CTRIO FAQ0055)
10-Mar-2003
Q: Are there any slot restrictions for the CTRIO if installed
in an EBC?
A: The following restrictions apply:
EBC FAQ0050 (see also
SDK FAQ0010)
14-Apr-2003
Q: Using the Ethernet SDK's EBCDemo.EXE but getting "????" for
analog module F2-08DA-2 installed in H2-EBC.
A: This is because the EBCDemo.EXE was created before the
F2-08DA-2 module was created; so it doesn't know exactly what it is.
Also make sure you have at least H2-EBC firmware version v2.1.128 to
support this newer analog module.
EBC FAQ0051 (see also
SDK FAQ0008)
03-Dec-2002
Q: Using the T1F-14THM thermocouple module; how do I convert the
returned hexadecimal value into a decimal temperature?
A: The EBC that the T1F-14THM module is plugged into has already
converted it to a temperature in the Visual Basic data type called
"long." But, if you want to convert a hexadecimal to a decimal number
you would use something like:
Val(string)
Where string is a hexadecimal number like "&H10FA."
EBC FAQ0052 (see also
DS Data FAQ0087; DirectSOFT FAQ0180; NetEdit FAQ0012; ECOM FAQ0040;
EDRV FAQ0010; ERM FAQ0034; EZ Ethernet FAQ0026)
27-Apr-2004
Q: Getting various errors when attempting to use NetEdit to see or
establish a link to a Host Ethernet device.
A: Here are know errors and their suggested solutions:
CAUTION: You may want to consult your Network Administrator before doing any of the solutions below! He/she may not want you to change your PC's setup at all!
(5) "Error reading
configuration values from device."
First of all, there was a bug in
versions of NetEdit previous to v3.1, that when you pressed the
Query Network button this error could pop up. If this is the case
then you just need to download a later copy (at least v3.1) of
NetEdit from our website. If this is not the case then
notoriously, this error is caused by one of the following:
If none of these things fix the
problem, then it is possible that the EBC/ECOM/EDRV/ERM/EZ Ethernet
device is defective and you may need to send it in for repair.
EBC FAQ0053 (see also
ERM FAQ0035)
14-Oct-2003
Q: When trying to download configuration from ERM Workbench to the
ERM get, "Error trying to reset ERM for download."
A: This is really nothing more than a timeout error and is more
than likely due to one of the following issues:
EBC FAQ0054 (see also
CTRIO FAQ0062; NetEdit FAQ0015)
02-Feb-2005
Q: Using an EBC100 and Modbus TCP protocol, how can I figure out
where the CTRIO parameters are mapped into the Modbus addresses?
A: The easiest way to do this is to use NetEdit3 and CTRIO
Workbench in combination. Follow these steps:
Here you can see that NetEdit3 has provided the Modbus addressing for you. Next you need only to see how these work in the CTRIO.
After manually entering these numbers from NetEdit3 into CTRIO Workbench's I/O mapping screen you can now see all the parameters and their appropriate Modbus TCP addressing.
EBC FAQ0055 (see also
ERM FAQ0036)
08-May-2002
Q: Analog reads on EBC can sometimes jump by +256.
A: This is due to a timing issue with newer 16AD modules and EBC
PLD chip. If this occurs return EBC to Host for modification.
EBC FAQ0056
07-Mar-2005
Q: What is the Node Address used for?
A: The Node Address of the EBC is just a text field stored in the
EBC.
- If the dipswitches are set to zero (all off), then the Node Address can be changed using NetEdit or Ethernet SDK.
- If the dipswitches are set to a non-zero value, then this non-zero value becomes the Node Address and it cannot be changed via software.
The Node Address was mainly created for Think&Do/Entivity software users. These software packages just use IPX protocol to talk to the EBC and therefore must know the EBC's MAC address. But by having dipswitches on the EBC this allows the Think&Do/Entivity user to buy an EBC, unpack it, set the Node Address via the dipswitches, hook it up and then write his application around the Node Address without having to know the rather cryptic MAC address of the EBC. Basically, behind the scenes Think&Do/Entivity software just sends a directed broadcast in IPX and finds the EBC, then reads its Node Address text field. It then reads the MAC address and associates this MAC address with the Node Address. This way the customer doesn't have to configure or even know the MAC address of the EBC. Also, if the EBC goes bad, he can simply replace this EBC with a new one that has the same dipswitch setting and he doesn't have to change his application to adjust for the new MAC address.
Thus for applications other than Think&Do/Entivity, the Node Address has no specific meaning.
EBC FAQ0057 (see also
DirectSOFT FAQ0183; DS Data FAQ0093; ECOM FAQ0043; EDRIVE FAQ0012; ERM
FAQ0037; EZ Ethernet FAQ0027; NetEdit FAQ0017)
27-Sep-2010
Q: How can I install IPX protocol for my NIC?
A: You can find instructions on how to do this for your
particular operating system by going to Start --> Help &
Support and searching for "Install NWLink." Below are the instructions
from Microsoft for doing this on a WinXP PC. The instructions are
similar for other operating systems (e.g. WinNT, Win98, WinME, Win2K).
To install NWLink IPX/SPX/NetBIOS
Compatible Transport Protocol
(1) Open Network Connections:
(a) Click Start
--> Settings --> Control Panel.
(b) Double-click Network
Connections.
NOTE: You must be a
member of the Administrators group to install protocols. Also, when
IPX is installed it is installed for all your connections. If you
don't want it installed for a certain connection, then right-click
that connection, click Properties and, on either the General
or Networking tab, clear the NWLink IPX/SPX/NetBIOS
Compatible Transport Protocol check box.
(2) Right-click a local area connection, then click Properties.
(3) On the General tab, click Install.
(4) In the Select Network Component Type dialog box,
click Protocol, and then click Add.
(5) In the Select Network Protocol dialog box, click NWLink
IPX/SPX/NetBIOS Compatible Transport Protocol, and then click OK.
IMPORTANT: The IPX/SPX protocol is not available on
WinXP 64-Bit Edition, WinVista or Win7.
EBC FAQ0058 (see also
ERM FAQ0039)
19-Aug-2005
Q: What is the limitation of I/O for the ERM / EBC configuration?
A: The ERM has a limit of 8K bytes (8192 bytes) of I/O data
from all of its EBCs. Each EBC has a data budget of 1400 bytes of I/O.
In other words you will probably run into other limitations before you
run into these limitations.
EBC FAQ0059 (see also
ECOM FAQ0051; EDRIVE FAQ0013; ERM FAQ0040; EZ Ethernet FAQ0028;
NetEdit FAQ0022)
22-Sep-2005
Q: I inadvertently changed the IP address of my Host Engineering
Ethernet device and now NetEdit cannot find it, nor can I ping it.
How can I get it "back?"
A: It can be changed using IPX protocol:
EBC FAQ0060 (see also
ERM FAQ0041; EDRIVE FAQ0014)
28-Sep-2005
Q: In ERM Workbench, what do the colors of the slave numbers in the
Slave Status box mean?
A: Colors indicate slave status of a particular slave:
COLOR | DESCRIPTION |
Grey | Slave not configured. |
Green | Slave configured and ERM successfully communicating with it. |
Yellow | Slave configured and ERM successfully communicating with it, but the slave has an error in its I/O. |
Red | Slave configured but ERM cannot communicate with it. |
EBC FAQ0061 (see also
ECOM FAQ0052; EDRIVE FAQ0015; ERM FAQ0042; EZ Ethernet FAQ0029;
HA-TADP FAQ0005; WinPLC FAQ0028)
29-Sep-2005
Q: Do any of your Ethernet devices support the next generation of
Internet (IPv6)?
A: No; nor do we have any plans to implement it at this
time.
EBC FAQ0062 (see also
ERM FAQ0043)
04-Oct-2005
Q: How does the F2-8AD4DA-1 and F2-8AD4DA-2 modules log into the
H2-EBC or H2-EBC100? And how is it configured?
A: This module logs in as 8 words in and 8 words out even
though it is really only an 8 word in and 4 word out module. The extra
4 words out are used to configure the module:
5th Word Out = Input resolution
6th Word Out = Input/Output range (F2-8AD4DA-2 only)
7th Word Out = Track & Hold
8th Word Out = <not used>
For the specific bit configurations of the above, see the manual for the module.
EBC FAQ0063
08-Nov-2004
Q: Using T1H-EBC100 with Modbus on the serial port; discovered that
the EBC100 is responding to all Modbus node addresses seen on the
wire.
A: This is a bug in the T1H-EBC100 firmware. It is fixed in
at least firmware v4.0.1288 or higher. The Modbus/RTU ID (over the
serial port) is now set to the Module ID of the T1H-EBC100. This
Module ID is set by the DIP switches on the module itself, or via
NetEdit3 software.
EBC FAQ0064
15-Dec-2004
Q: Due to a limitation of a Modbus TCP master, cannot address the
50000+ range in the T1H-EBC100 to configure the analog cards.
A: For this very reason, the T1H-EBC100 mirrors the 50000+ range
to the 410000+ range. This means writing to the Holding Register range
(Function Code 06) of 40000 with an offset of 10000 or greater.
EBC FAQ0065 (see also
ECOM FAQ0053; EDRV FAQ0017)
20-Feb-2009
Q: Using a 3rd-party Modbus TCP master (e.g. Wonderware), when
multiple requests are sent to the ECOM100, EBC100, or EDRV,
sometimes some of the packets timeout.
A: The firmware of these devices were originally set up to do one
transaction at a time. Multiple requests to different TCP port numbers
was not a problem. This problem was fixed in:
H0-ECOM100 firmware version 4.0.52 (or
later)
H2-ECOM100 firmware version 4.0.999 (or later)
H2-EBC100 firmware version 4.0.464 (or later)
T1H-EBC100 firmware version 4.0.1309 (or later)
GS-EDRV firmware version 1.1.267 (or later)
EBC FAQ0066 (see also
CTRIO FAQ0069)
26-Jul-2005
Q: When using H2-CTRIO in H2-EBC100, the Output Active bit for the
CTRIO doesn't come on, however, it works in an H2-EBC.
A: This is a bug caused by the firmware of the H2-EBC100. The
DWORD outputs were not getting written to the CTRIO properly. It is
fixed in:
H2-EBC100 firmware v4.0.457 or higher.
EBC FAQ0067 (see also
ECOM FAQ0054)
30-Sep-2005
Q: Does the EBC100 or the ECOM100 support Allen-Bradley Ethernet/IP
protocol?
A: No. However, both the EBC100 and the ECOM100 support Modbus
TCP. Prosoft Technology makes a Modbus TCP card that plugs into
Allen-Bradley systems that could be used to talk to them.
EBC FAQ0068
14-Oct-2005
Q: Using Modbus TCP Master to a T1H-EBC100, if read requests for
the I/O Module Status data are not on the 20-word boundaries,
erroneous data is returned.
A: This is a bug in the firmware of the T1H-EBC100. It is fixed
in:
T1H-EBC100 firmware v4.0.1309 or higher.
EBC FAQ0069 (see also
ECOM FAQ0055; EDRIVE FAQ0018; ERM FAQ0044; EZ Ethernet FAQ0030;
HA-TADP FAQ0006; WinPLC FAQ0032)
15-Nov-2005
Q: What types of Ethernet framing do your Ethernet products
support?
A: All our Ethernet products (ECOM, ECOM100, EBC, EBC100, EDRV,
ERM, EZ Ethernet, EZ EtherPLUS, HA-TADP and WinPLC) all support the
following types of Ethernet framing:
EBC FAQ0070 (see also
ECOM FAQ0061; EDRIVE FAQ0019; ERM FAQ0045; EZ Ethernet FAQ0031;
HA-TADP FAQ0007; WinPLC FAQ0033)
22-Feb-2005
Q: Are the Host Engineering Ethernet products compliant to AS ISO
15745?
A: No.
EBC FAQ0071 (see also
ERM FAQ0046; SDK FAQ0014)
09-Aug-2005
Q: Why can I not see negative temperatures with my T1F-14THM and
T1F-14RTD modules?
A: This is because of a fundamental design difference between the
THM/RTD modules and all other analog modules in Terminator I/O.
Technically all other analog modules in the Terminator I/O line output
24-bit data onto the Terminator I/O bus. The T1H-EBC/T1H-EBC100 looks
at the 24th bit and then sign extends this bit to the 32nd bit. This
allows 32-bit negative numbers to be viewed from all other analog
modules. However, the T1F-14THM and T1F-14RTD modules only output
16-bit data onto the Terminator I/O bus. Thus when the
T1H-EBC/T1H-EBC100 looks at the 24th bit, it never sees this bit set,
and so the sign extension is always with a cleared bit to the 32nd
bit. Thus all 32-bit negative numbers from this configuration will
always be positive. Some suggested solutions are given below this
diagram:
Therefore, whatever is reading the values of the THM/RTD module from the EBC/EBC100 will have to manipulate the data in order to make it negative. For example:
EBC FAQ0072 (see also
CTRIO FAQ0072; ERM FAQ0047; SDK FAQ0015)
09-Jan-2006
Q: In my H2-ERM/H2-EBC (or H2-EBC100) configuration, the H2-CTRIO
word output (WO) and double-word output (DWO) mapping is different
than where CTRIO Workbench indicates they should be.
A: This is caused by an I/O mapping problem in the H2-EBC and
H2-EBC100 that is fixed in EBC firmware v2.1.441 and later. It has to
do with the H2-CTRIO "I/O type." The H2-CTRIO is now reported as a
Type 7 module instead of a Type 5 module. This new reclassification of
the H2-CTRIO as a Type 7 allows the EBC to manage the order in which
things get mapped.
The symptom shows up as a mapping discrepancy in the order in which the CTRIO puts the DWOs and the WOs VS where the ERM Workbench maps them in PLC memory.
For example, for comparison see the chart below:
H2-CTRIO Mapping Component | H2-CTRIO mapping in H2-EBC (H2-EBC100) with firmware less than v2.1.441 | H2-CTRIO Mapping in H2-EBC (H2-EBC100) with firmware v2.1.441 or later |
96 Discrete Input (DI) | X340-477 (V40416-40423) | X340-447 (V40416-40423) |
96 Discrete Output (DO) | Y320-457 (V40515-40522) | Y320-457 (V40515-40522) |
12 Word Output (WO) | V2100-2113 | V2110-2123 |
8 Double Word Input (DWI) | V2000-2017 | V2000-2017 |
4 Double Word Output (DWO) | V2114-2123 | V2100-2107 |
NOTE: If you update the EBC firmware to fix this problem, make sure that you are at least using CTRIO Workbench v2.1.10 to configure the H2-CTRIO.
EBC FAQ0073
21-Feb-2006
Q: Using T1H-EBC100 and Modbus TCP, I can't write to the
Cofiguration Words (50021-50053) for my T1F-8AD4DA-x combo analog
module.
A: This is a bug in the T1H-EBC100 firmware, and it is fixed in
version 4.0.1313.
EBC FAQ0074
21-Feb-2006
Q: Using T1H-EBC100 and the incorrect I/O shows up in the
addressing (Type 13).
A: This is a hardware bug in the T1H-EBC100 which prevents 16pt
Discrete I/O modules from being logged into the system correctly. The
most common symptom of this problem occurrs if you have a 16pt
Discrete Input module followed by a 16pt Discrete Output module. The
T1H-EBC100 would show both of these modules logged into the same slot
with a module ID of 13.
This bug is fixed in T1H-EBC100 PWB Rev: 6E.
This fix cannot be applied in the field,
you must return the T1H-EBC100 to have the unit serviced. There are two
options available to have the T1H-EBC100 fixed:
1. If you purchased the unit less than 30 days ago, you can return it to
Automationdirect.com through their normal RMA processing system for a
replacement.
2. If you purchased the unit more than 30 days ago, you can contact us
here at Host Engineering via email for instructions on how to ship the
unit directly to us for repair. Send the email inquiry to
support@hosteng.com.
NOTE: This fix is for a very specific hardware related issue. Use the
"Show Base Contents" option in NetEdit v3 to verify that adjacent 16pt
Discrete I/O modules are showing up in the same slot with the Module ID
of 13 before you contact us for a replacement or to have the unit
repaired.
EBC FAQ0075 (see also
NetEdit FAQ0030)
18-Nov-2008
Q: What are the meanings of the Port Mode settings for the
EBC/EBC100 that are seen in Serial Port Settings of NetEdit?
A: The functionality and description of these modes are not
documented anywhere simply because there are no products that fully
utilize them. Basically the EBC has 2 Port Modes (Master/Proxy; K-Seq
Slave) and the EBC100 has an extra 3rd one (Modbus Slave). These modes
are briefly described here:
EBC FAQ0076 (see
also NetEdit FAQ0032; ECOM FAQ0092; EDRV FAQ0023; ERM FAQ0050; )
23-May-2007
Q: Can firmware upgrades be performed over a remote network (e.g.
over the Internet)?
A: Not normally, no. The reason is because NetEdit must be able
to see the Host Ethernet device in his list. The list is compiled by
NetEdit sending out a broadcast and having all the Host Ethernet
devices respond. Since the Internet will block all broadcasting, then
the list will always be blank. However, it is possible to configure a
VPN (Virtual Private Network) between the locations and configure the
VPN in such a way as to allow broadcasting.
EBC FAQ0077 (see
also ECOM FAQ0102; ERM FAQ0051; SDK FAQ0019; NetEdit FAQ0034)
24-Jul-2013
Q: How can I enable the "fast response mode" of the T1F-08AD-1 or
T1F-08AD-2?
A: The fast response mode of these devices is activated by a
write to a special location in the T1H-EBC or T1H-EBC100 called Config
Data. This area of memory is not available to the ERM nor NetEdit and
therefore cannot be configured with ERM
Workbench, nor NetEdit.
If using T1H-EBC:
- Currently, the only way to write to the Config Data of the T1H-EBC
is to use the Ethernet SDK routine HEIWriteConfigData. The Ethernet
SDK is free and downloadable from
http://www.hosteng.com/Ethernet_SDK.htm.
If using T1H-EBC100:
- Currently, there are 2 ways to write to the Config Data of the
T1H-EBC100:
(1) Use the Ethernet SDK routin
HEIWriteConfigData. The Ethernet SDK is free and downloadable from
http://www.hosteng.com/Ethernet_SDK.htm.
(2) Use Modbus TCP. The Config Data is mapped
into the Modbus TCP memory range 50021-50052 (or 410021-410052 for
6-digit addressing). This range is 32 words (1 word for each slot).
The bits of the word are defined as follows for the analog input
cards:
Bits 0-4: 0 = All channels enabled; 1-31 = Number of channels enabled starting with channel 1
Bits 5-6: Reserved
Bit 7: 0 = Normal response; 1 = Fast response
Bits 8-15: Reserved
EBC FAQ0078 (see also
NetEdit FAQ0004; ECOM FAQ0025; EDRV FAQ0011; ERM FAQ0052; EZ Ethernet
FAQ0007)
27-Jan-2010
Q: Can retries and timeout values for NetEdit be adjusted to allow
it to find Host Ethernet devices on much slower networks?
A: No, but we will probably include this ability in future
releases of NetEdit (greater than v3.7). Currently NetEdit sends out a
broadcast and waits 600 ms for devices to respond. If the devices take
longer than this to respond they will be missing from his list. After
the responses are gathered, NetEdit makes a list and then polls each
device in the list one at a time to get detailed data, but waits only
250 ms for response from each device. If the device takes longer than
this to respond some of its data may be missing. This is not a problem
on a normal wired network, but can be a problem on a wireless network
or across the Internet where responses can inadvertently be long and
inconsistent. Also, since a broadcast is used, any device between
NetEdit and the Host Ethernet modules that block broadcasts can
prevent NetEdit from seeing anything.
EBC FAQ0079 (see also
WinPLC FAQ0036; CTRIO FAQ0012)
26-Mar-2010
Q: When trying to connect to CTRIO/CTRIO2 in WinPLC or EBC/EBC100
base with CTRIO Workbench, getting "Error reading base definition".
A: This is usually caused by the CTRIO Workbench not having enough
of the backplane bandwidth to complete a connection. Thus, depending
on what type of base the CTRIO/CTRIO2 is installed in:
If WinPLC: Try stopping the WinPLC's application from running; then try CTRIO Workbench again.
If EBC/EBC100: Try stopping the master that is currently polling, or disconnect from the master altogether; then try CTRIO Workbench again.
If none of this works, try reinstalling CTRIO Workbench. There have been instances where something on the PC has corrupted the installation and caused this very error message.
EBC FAQ0080 (see also
ECOM FAQ0104)
02-May-2008
Q: If multiple Modbus TCP masters (or connections) are talking to a
single ECOM100 or EBC100, and the communication happens to be
interrupted (e.g. cable break; radio comm error), then on rare
occasions the ECOM100 or EBC100 will fail (red ERR light comes ON).
A: This is caused by a bug in the ECOM100 / EBC100 firmware in the
are of the TCP stack code. This bug was fixed in firmwares:
H0-ECOM100 v4.0.222 (or later)
H2-ECOM100 v4.0.1444 (or later)
H4-ECOM100 v4.0.1444 (or later)
H2-EBC100 v4.0.518 (or later)
T1H-EBC100 v4.0.1325 (or later)
EBC FAQ0081 (see
also ERM FAQ0056; EDRV FAQ0026)
25-Mar-2009
Q: Trying to use the example in B-2 of the ERM Manual to reset
errors in the EDRV and EBC/EBC100, but X330 (ERM Disable Request
Bit) of the ERM Status Word never comes ON.
A: This is a bug in older versions of the ERM firmware.
The ERM Status Word contains the current ERM Error Code in the LSByte and the Status Bits in the MSByte. Currently, only bit 8 (X330) is used in the MSB designating the ERM is disabling a Slave. Earlier versions of the ERM firmware was incorrectly handling this feedback bit. This is fixed in the following firmware:
H2-ERM
v1.1.19 (or later)
H4-ERM v1.1.19 (or later)
EBC FAQ0082 (see also CTRIO FAQ0026; PBC
FAQ0013; WinPLC FAQ0037)
17-Nov-2015
Q: Why are the I/O Map values not saved if using CTRIO Workbench to
talk to a CTRIO in an EBC/EBC100, WinPLC, or PBC base?
A: If the CTRIO/CTRIO2 is in any of these bases, the values
entered in the CTRIO Workbench I/O Map do not
determine the CTRIO's I/O address mapping. Something other than the
CTRIO/CTRIO2 itself is determining this mapping (see chart below).
Thus the I/O Map, in these cases, is merely a documentation function.
If you enter values in this map, they will not be saved in the CTRIO/CTRIO2's .CWB file that you might create. Thus, to remember the values, you will have to use the Report button at the bottom and then either Print a hard copy, or Save it to a .TXT file.
BASE CONTROLLER | MASTER OF THE BASE CONTROLLER | I/O MAPPING DETERMINED or SHOWN BY: |
DL05 | N/A | CTRIO Workench (I/O Map) |
DL06 | ||
DL205 | ||
DL405 | ||
Do-more (H2-DM1, H2-DM1E, T1H-DM1,
T1H-DM1E) |
Do-more
Designer CTRIO Structure Members |
|
H2-EBC, H2-EBC100, H4-EBC |
PC (Ethernet SDK) | H2-EBC, H2-EBC100, H4-EBC (NetEdit --> Show Base Contents) |
PC (KepDIRECT EBC) | ||
PC (Think&Do or Entivity) | ||
H2-ERM, H2-ERM100, H4-ERM |
ERM Workbench (Configure ERM/ERM100) | |
Do-more
Ethernet I/O |
Do-more Designer CTRIO Structure Members | |
H2-EBC100 only | 3rd-party (Modbus TCP) | H2-EBC100 (NetEdit --> Show Base Contents) |
H0-ECOM100, H2-ECOM100, H4-ECOM100 (Modbus TCP) | ||
Do-more
(Modbus TCP) |
||
H2-WPLC (Think&Do or Entivity) | <N/A> | H2-WPLC (Think&Do or Entivity) |
H2-WPLC (WinCE) | H2-WPLC (3rd-party application) | |
H2-PBC | 3rd-party (Profibus Master) | 3rd-party (Profibus configurator) |
T1H-EBC or T1H-EBC100 | PC (Ethernet SDK) | T1H-EBC or T1H-EBC100 (NetEdit --> Show Base Contents) |
PC (KepDIRECT EBC) | ||
PC (Think&Do or Entivity) | ||
H2-ERM, H2-ERM100, H4-ERM |
ERM Workbench (Configure ERM/ERM100) | |
Do-more
Ethernet I/O (H2-DM1E, T1H-DM1E) |
Do-more Designer CTRIO Structure Members | |
T1H-EBC100 only | 3rd-party (Modbus TCP) | T1H-EBC100 (NetEdit --> Show Base Contents) |
H0-ECOM100, H2-ECOM100, H4-ECOM100 (Modbus TCP) | ||
Do-more (Modbus TCP) |
NOTE: To use the table, note what is controlling the base where the CTRIO/CTRIO2 is plugged into. Then note what is controlling the base controller itself. In the last column is the device or software that either determines the I/O mapping, or at least shows it to you.
EBC FAQ0083 (see also
CTRIO FAQ0045; DirectSOFT FAQ0132; DL Plus FAQ0010; DNLoader FAQ0011;
DS Data FAQ0102; ECOM FAQ0084; EDRV FAQ0084; ERM FAQ0058; EZ Ethernet
FAQ0010; General FAQ0004; HA-TADP FAQ0008; Lookout Direct FAQ0015;
NetEdit FAQ0037; PBC FAQ0014; PSCM FAQ0003; SDK FAQ0022; SERIO
FAQ0004; WinPLC FAQ0038)
31-Dec-2009
Q: What is the export classification of your products (e.g. ECCN)
A: None of our products have an ECCN. Automation Direct sells our
products and they export EAR99 NLR (No License Required). ECCN
is Export Controlled Classification Number and none of our
products are controlled.
EBC FAQ0084
23-Feb-2010
Q: What is the function of the battery in the H4-EBC?
A: There is no currently sold product that utilizes the battery.
But technically it provides the following functions:
EBC FAQ0085 (see also
ECOM FAQ0099; EDRV FAQ0028; EZ Ethernet FAQ0013)
19-May-2010
Q: Do Host Ethernet devices use full- or half-duplex
communications?
A: Half-duplex, allowing alternating transmission in 2
directions, but not in both directions simultaneously.
EBC FAQ0086 (see also
ECOM FAQ0114, EDRV FAQ0029, ERM FAQ0060, EZEthernet FAQ0032, NetEdit
FAQ0040)
11-Feb-2011
Q: What do the Ethernet Stats at the bottom of NetEdit
specifically mean?
A: These are stats that are reported up to the firmware from
the hardware communication components. They are technically defined
as:
Missed Fr - "Missed Frames" - A count of the packets missed due to overruns, unavailable buffers or a disabled receiver.
TX Coll - "Transmit Collisions" - A count of the packets which had a late collision while being received.
Lost Pkts - "Lost Packets" - A count of the packets discarded because they were too long or too short.
Bad Pkts - "Bad Packets" - A count of the packets which have bad CRCs (checksums).
Unknown - A count of the packets which contain invalid symbols, extra bits or resulted in a receiver overrun condition.
TX Errors - "Transmit Errors" - A count of the packets which could not be sent because the transmitter was unavailable for an extended period of time.
Link Monitor Timeout Value | Meaning |
0 (zero) | Default value. If communication with master is lost, EBC100 freezes outputs. |
1-65,535 | Timeout value in milliseconds (ms). If communication with master is lost for this amount of time, EBC100 turns all outputs OFF |
These fixes are in:
H2-EBC100 v4.0.490 (or later)
T1H-EBC100 v4.0.1322 (or later)
H0-ECOM100 v4.0.167 (or later)
H2-ECOM100 v4.0.1237 (or later)
H4-ECOM100 v4.0.1237 (or later)
GS-EDRV100 v5.0.218 (or later)
NetEdit v3.7
EBC
FAQ0092 (see
also ECOM FAQ0118, EDRV FAQ0032, ERM FAQ0065)
31-Mar-2014
Q: What
does a flashing/blinking Err light indicate?
A: This is an
indication of a fatal error. The blink codes specifically mean:
We, therefore suggest that consideration be given to using a Do-more PLC instead.
EBC
FAQ0094 (see
also ERM FAQ0067)
28-May-2014
Q: In ERM Workbench getting
intermittent "Slave 1: Error (9)
- Communications error - timeout".
A: This is an
extremely rare error that actually means the ERM100 master is
receiving NAKs (Negative Acknowledgements) from the EBC100.
Consequently, that means the telegram the EBC100 received from the
ERM100 was not understandable (i.e. an invalid request). Since the
ERM100 doesn't send out invalid requests, this most likely is a noise
issue on the network. Possible solutions:
MODULE | FIRMWARE RELEASE |
*DIPSWITCH | |||||||
7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | ||
H0-ECOM | v1.0.354 | RBE | Module ID | ||||||
v1.0.364 | **Protect | Module ID | |||||||
H0-ECOM100 | v4.0.49 | RBE/IBox | *Recover | Module ID | |||||
v4.0.320 | **Protect | Module ID | |||||||
H2-ECOM H2-ECOM-F H4-ECOM H4-ECOM-F |
v1.0.7 | Module ID | |||||||
v1.0.147 | RBE | Module ID | |||||||
v1.0.227 | **Protect | Module ID | |||||||
H2-ECOM100 H4-ECOM100 |
v4.0.877 |
RBE/IBox | *Recover | Module ID | |||||
v4.0.1735 | **Protect | Module ID | |||||||
H2-ERM H2-ERM-F H4-ERM H4-ERM-F |
v1.1.1 | Module ID | |||||||
H2-ERM100 H4-ERM100 |
v4.0.73 | *Recover |
Module ID | ||||||
H2-EBC H2-EBC-F |
v2.1.80 | Module ID | |||||||
H2-EBC100 | v4.0.447 | *Recover | Module ID | ||||||
H4-EBC H4-EBC-F |
v2.1.1 | Module ID | |||||||
T1H-EBC | v1.0.386 | ||||||||
T1H-EBC100 | v4.0.1260 | *Recover | |||||||
GS-EDRV | v1.1.24 | Module
ID |
|||||||
GS-EDRV100 | v5.0.218 | *Recover |
Module
ID |
||||||
MB-GATEWAY | v1.0.601 | *Recover |
Stop
Bits |
Parity |
Baudrate |